XLPE SUBMERCIBLE

ITEM CODE SIZE PARTICULARS CORE MRP
90086 1.5sq mm 22/.03 MM 3 5880.00
90087 2.5sq mm 36/.03 MM 3 8860.00
90088 4.0sq mm 56/.03 MM 3 13050.00
90089 6.0sq mm 84/.03 MM 3 18970.00
90090 10.sq mm 140/.03 MM 3 31830.00
90091 16sq mm 226/.03 MM 3 50560.00
90092 25sq mm 354/.03 MM 3 76520.00

3 CORE FLAT CABLES WITH COPPER CONDUCTOR XLPE INSULATION AND HR PVC SHEATH

TECHNICAL DATA
. Conductor : Flexible annealed electrolytic grade copper .Voltage Grade: Upto and including 1100V ac 50Hz 3Ph
. Insulation : Cross linked Polyethylene (XLPE) . Temperature: Max conductor temperature of 90°C
.Sheath : Heat Resistant PVC Type ST2 (as per IS 5831:1984) . Specification: Generally as per IS 7098 (Part 1) 1988
SR No. PARAMETER Size (Sq. mm)
1.5 2.5 4 6 10 16 25 35
1 Conductor construction (No./mm) 22/0.30 26/0.30 56/0.3 84/0.3 140/0.3 226/0.3 354/0.3 495/0.3
2 Conductor Resistance at 20°C max 12.1 7.41 4.95 3.3 1.91 1.21 0.78 0.554
3 Insulation Thikness (mm) Nom. 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9
4 Sheath Thickness(mm) Nom. 0.9 1 1 1.1 1.2 1.3 1.5 1.6
5 Overall Dimensions (mm) Approx. Width(W) 11.1 12.7 14.9 16.9 20.3 23.8 29.6 33.6
Height (H) 5.3 6 6.6 7.4 9.1 10.4 12.9 14.4
The Number of Wires and its diameter in the conductor will be such as to satisfy requirement of the conductor resistance as per IS 8130:1984
Current Carrying Capacity (Amps) And Derating Factors
SR No. CABLE TYPE Size (Sq. mm)
1.5 2.5 4 6 10 16 25 35
1 PVC Insulation 14 18 26 31 42 57 72 90
2 XLPE Insulation 25 30 37 46 66 85 113 139
Ambient Temperature (Deg. C) 25 30 35 40 45 50
Rating Factor 1.18 1.12 1.06 1 0.94 0.88

Airson make three core flat cables are best suited for submersible application and manufactured with conductor using annealed bare copper wires of electrolytic grade, bunched properly to ensure desired flexibility. The conductor is further insulated with thermoset type Cross Linked Polyethylene (XLPE) with uniform thickness with each each of the core colours in red, yellow, and blue by using most modern machinery and extrusion techniques. The sheath with uniform thickness of heat and moisture Resistant type PVC (Grade ST2) compound formulated and manufactured inhouse, is extruded over these coloured cores in a flat formation. The colour of the sheath is black. The cables undergo stringent quality checks during raw materials, in process and final testing as per the laid down specification and the quality norms. The cables are available with progressive sequential marking, company name size & voltage printed on sheath. following are the advantages offered by XLPE insulated cable over the PVC insulated cables.